Switching Standard AC Power Supply Apa1000 Series

time2024-11-06
parameters

• Input voltage range: single-phase 195~245V three-phase 340V ~ 420V
• Input frequency range: 50/60Hz ± 5%
• Output voltage range: single-phase 0~300V (0~600V optional) three-phase 0~520V (0~1040V optional)
• Output frequency range: 45~500Hz
distortion rate ≤ 1% Voltage stabilization rate ≤ 1% Frequency stability ≤ 0.01%
• Can simulate the test environment grid situation of various countries in the world

High performance characteristics
• Single-phase power supply maximum capacity can be 600KVA, three-phase power up to 2000KVA
• Ultra strong crest factor ratio up to 3.5:1
• Fast response for special loads. Low Distortion Interference, Full Input/Output Isolation
• Terminal voltage feedback compensation function to ensure that the test power without error
• Waveform start angle can be set (0~359 °), with synchronous source signal interface
• Fast computing speed, providing accurate and fast power parameter measurement
• Using single chip microcomputer (D/A circuit) to directly collect voltage and current waveform data. Contains RS232 or RS485 interface, can communicate with the computer, there are five kinds of serial port baud rate choice.
• The use of central processor design, control the opening and closing of the logic circuit. The one-to-one driving method is used to facilitate the dispersion and heat dissipation of the power components, and the structure is conducive to the "redundant" design.
• Choose to use voltage analog quantity (0~5V) or current analog quantity (4 ~ 20mA) to control the power output
Perfect protection function: overload, overcurrent, over temperature, short circuit, undervoltage protection and alarm
• LCD display parameters: voltage, current, power, power factor, frequency, peak current and time
• LED display voltage, current, frequency, power (power factor)
A single test group can perform 35 test points (different voltage 0~300V, frequency 45~500Hz, time 0.1S ~ 999.9H setting), and can continuously do cyclic tests (0~999999 times).

APA1000 single-phase series

Model10001001100210031005101010151020
Output capacity500VA1KVA2KVA3KVA5KVA10KVA15KVA20KVA
Input1Ø2W+G 110V/220V±10% or 220V±10%3Ø4W+G 220V/380V±10%
50/60Hz ± 5%
Output frequency50Hz 60Hz 47~63Hz (45~500Hz optional)
frequency stability0.01 percent
Output voltage0~150V/0~300V
Output current4.2/2.18.4/4.216.8/8.425/12.542/2184/42126/63168/84
Load regulation rate≤ 1%
harmonic distortion≤1% (full load≤2%)
Meter displayLED/LCD display voltage current frequency power (power factor)
Protection deviceOverload, overcurrent, temperature, short circuit, undervoltage protection and alarm
Weight (kg)2025303545100115130
Dimensions (mm)W * H * D425*89*480430*200*500430*490*700430*580*700
Working environmentAmbient temperature 0~40°C Relative humidity 10 ~ 90%

APA1000S three-phase series

Model1015s1020s1030s1045s1060s1075s1100s1120S
Output capacity15KVA20KVA30KVA45KVA60KVA75KVA100KVA120KVA
Input1Ø2W+G 220V±10%3Ø4W+G 220V/380V±10% 50/60Hz±5%
Output frequency50Hz 60Hz 47~63Hz (45~500Hz optional)
frequency stability0.01 percent
Output voltagePhase voltage 0V ~ 150V/0~300V Line voltage 0V ~ 260V/0~520V
Output current42/2154/2784/42126/63168/84210/105278/139333/166
Load regulation rate≤ 1%
harmonic distortion≤1%(full load≤2%)
Meter displayLED/LCD display voltage current frequency power (power factor)
Protection deviceOverload, overcurrent, overcurrent, temperature, short circuit, undervoltage and phase loss protection and alarm
Weight (kg)210240360450540600780850
Dimensions (mm)W * H * D510*780*710430*200*500750*1500*850900*1780*950

Measurement function

ProjectResolution (4 bits)Accuracy
frequency table0.01Hz/0.1Hz Auto Range±0.1% reading±2c±0.05%/100Hz
voltmeter0.1V±0.2% reading±0.3% Full scale±2c±0.1%/100Hz
Ammeter1mA/10mA 10mA/100mA Auto Range±0.4% reading±0.3% Full scale±3c±0.1%/100Hz
power meter0.1W/1W 1W/10W 10W/100W Auto Range±0.2% reading±0.2% Full scale±5c(at50/60Hz)
±0.3% reading±0.2% Full scale±5c±0.1%/100Hz
power factor meter0.001± 0.001